Investigating Impact of Indoor Temperature on the Performance of the Retail Commercial Refrigeration System

Brownbridge, Oliver, Sully, Matthew, Noons, Joshua and Albayati, Ibrahim (2022) Investigating Impact of Indoor Temperature on the Performance of the Retail Commercial Refrigeration System. International Journal of Air-Conditioning and Refrigeration, 30 (2). ISSN 2010-1325

Full content URL: https://doi.org/10.1007/s44189-022-00001-9

Documents
Investigating Impact of Indoor Temperature on the Performance of the Retail Commercial Refrigeration System
Published Open Access manuscript
[img]
[Download]
[img]
Preview
PDF
08b4f14b-5d98-4869-94ef-6d7e46e10d6a.pdf - Whole Document
Available under License Creative Commons Attribution 4.0 International.

7MB
Item Type:Article
Item Status:Live Archive

Abstract

Commercial food outlets in the UK are responsible for 3% of the UK total energy consumption, with refrigeration systems account for 29% of this total. In this paper, a validated model that simulates a commercial refrigeration system installed over 2000 sqft to mimic a real express store installed at Riseholme Refrigeration Research Centre at the University of Lincoln, UK, is presented. Investigations are conducted to examine different failures of air-conditioning (AC) systems and their impacts on the indoor store temperature, and hence on the refrigeration performance and energy consumption. Three different scenarios were examined: gradual increase in store temperature caused by an AC system with reduced performance, sudden increase in store temperature caused by a drastic AC failure, and fluctuations in store temperature caused by a faulty AC system. The results of the investigation for different failure scenarios of the AC system during 3 hours of continual operation showed an increase in the energy consumption of the refrigeration system by 17.4 % as a result of gradual AC failure, 33.6% for the sudden failure, and 5.3% for the intermittent failure. It is concluded that the AC failures caused the power drawn to increase due to spending a prolonged period of time at higher temperatures than during the normal AC operation. Also, the frequency which the compressors switch on and off increases the level of wear on the compressors. Both gradual and sudden failures of the AC system show a sustained increase in temperature leads to greater duty cycle for the expansion valve to increase the amount of refrigerant available. It is found that the sudden failure of the AC system had the greatest impact on the system, as the temperature of the store rises quickest, the display cases are exposed to higher temperatures for a longer time, this causes the greatest demand on the system and so lead to the largest power consumption. It is notable that for all three failure types that the product temperature experiences no noticeable fluctuations and remains comfortably within the temperature boundaries between 3 °C and 1 °C, as the system is able to provide an adequate cooling.

Keywords:Modelling and Simulation, Commercial Refrigeration System, AC Failure, Store Temperature, Power Consumption
Subjects:H Engineering > H390 Mechanical Engineering not elsewhere classified
Divisions:College of Science > School of Engineering
Related URLs:
ID Code:48400
Deposited On:03 Mar 2022 11:34

Repository Staff Only: item control page