Impact of the Generation System Parameters on the Frequency Response of the Power System: A UK Grid Case Study

Atkinson, Jovi and Albayati, Ibrahim M. (2021) Impact of the Generation System Parameters on the Frequency Response of the Power System: A UK Grid Case Study. Electricity, 2 (2). pp. 143-157. ISSN 2673-4826

Full content URL: https://doi.org/10.3390/electricity2020009

Documents
Impact of the Generation System Parameters on the Frequency Response of the Power System: A UK Grid Case Study
Published Open Access manuscript
[img]
[Download]
[img]
Preview
PDF
electricity-02-00009-v2.pdf - Whole Document
Available under License Creative Commons Attribution 4.0 International.

5MB
Item Type:Article
Item Status:Live Archive

Abstract

The operation and the development of power system networks introduce new types of stability problems. The effect of the power generation and consumption on the frequency of the power system can be described as a demand/generation imbalance resulting from a sudden increase/decrease in the demand and/or generation. This paper investigates the impact of a loss of generation on the transient behaviour of the power grid frequency. A simplified power system model is proposed to examine the impact of change of the main generation system parameters (system inertia, governor droop setting, load damping constant, and the high-pressure steam turbine power fraction), on the primary frequency response in responding to the disturbance of a 1.32 GW generation loss on the UK power grid. Various rates of primary frequency responses are simulated via adjusting system parameters of the synchronous generators to enable the controlled generators providing a fast-reliable primary frequency response within 10 s after a loss of generation. It is concluded that a generation system inertia and a governor droop setting are the most dominant parameters that effect the system frequency response after a loss of generation. Therefore, for different levels of generation loss, the recovery rate will be dependent on the changes of the governor droop setting values. The proposed model offers a fundamental basis for a further investigation to be carried on how a power system will react during a secondary frequency response.

Keywords:demand side response, frequency response, frequency stability, generation system, National Grid
Subjects:H Engineering > H631 Electrical Power Generation
H Engineering > H630 Electrical Power
Divisions:College of Science > School of Engineering
Related URLs:
ID Code:44639
Deposited On:26 Apr 2021 15:48

Repository Staff Only: item control page